|
Posted by blueman on August 11, 2005, 1:25 pm
> On 10 Aug 2005 07:20:01 -0700, "deans@wdeans.com"
>
> >Greetings,
> >
> >What does the NEC say about repairing damaged wire insulation inside of
> >a utility box? Is electrical tape acceptable so long as the colours
> >match? Is heat shrink tubing acceptable? Should I wire nut be used
> >even if the wire is shortened to only a couple inches instead of the
> >minimum 6? Is the only acceptable means to re-run the length of cable
> >between the two boxes? What is legal and what is the best most
> >accepted way even if it is not strictly legal?
> >
> >Thank you for your time,
> >William
> >
> >PS: Scenario is that a tenant decided to replace an ungrounded
> >receptacle with a receptacle w/ ground hole (but still without true
> >ground). Apparently the tenant had the receptacle around but no 2-3
> >prong converter and no car. They needed the ground plug for a power
> >strip for the entertainment center they were setting up. The tenant
> >did not properly pack the wires back into the box and put an outlet
> >mounting screw through hot wire insulation resulting in a short (but no
> >damage to the copper within the wire). Yes, yes, I am well aware that
> >what they were doing is wrong.
>
> As long as the rating matches or exceeds the insulation on the wire,
> you can use electrical tape (most does). I know this because I was
> prepared to take exception to something I saw a contractor doing but
> had the presence of mind to check the code book and found he was
> right! A little research saved embarrasment in that case.
>
> Dan
Just out of curiousity, what does the NEC allow if the insulation (but
not the wire) is nicked outside of a box -- i.e. along a run.
|