Can romex be incased in pvc underground I say no but a friend says yes A
steak is on the line...
Posted by RBM on October 30, 2009, 10:28 pm
> Can romex be incased in pvc underground I say no but a friend says yes A > steak is on the line...
A buried conduit is considered a wet location. NM cable is for dry
locations. Make it a Filet
Posted by Doug Miller on October 31, 2009, 12:19 am
>Can romex be incased in pvc underground I say no but a friend says yes A >steak is on the line...
Your friend owes you a steak. "Romex", correctly known as Type NM Cable, is
not permitted in wet locations. An underground conduit is considered a wet
location.
Posted by John Grabowski on October 31, 2009, 8:56 am
> Can romex be incased in pvc underground I say no but a friend says yes A > steak is on the line...
*No Romex underground, even in conduit. Make mine medium well.