|
Posted by deans@wdeans.com on September 10, 2006, 10:41 am
>
> > Greetings,
> >
> > Part A:
> > I have 240V baseboard heaters with the termostat inside the heater. I
> > want to put wall switches in the same place as the light switches so
> > that I can turn off the heaters when I leave the room without getting
> > down on the ground to adjust the thermostat. I know that a single pole
> > switch will work but I wanted to know if there was any reason the code
> > required a double pole switch? Thanks!
> >
> > Part B:
> > The baseboard heaters are 2000W. If I put 2 of them on the same 20A
> > circuit I am at 83% of the rated breaker capacity (I am using standard
> > Siemens breakers). Do I really need to put each one on its own
> > breaker?
> >
> > Thank you for your time,
> > William
> >
RBM (remove this) wrote:
> You can't exceed 80%, so you could use 30 amp wire. A wall thermostat or
> switch needs to disconnect both hot legs
Greetings,
You cannot exceed 80% of the wire rating or of the breaker rating? I
thought it was of the breaker rating? And my real question is: are
baseboard heaters considered intermittent loads?
Thanks,
William
|