Posted by sweetft5 on July 18, 2006, 3:30 pm
I have a sprinkler system with three zones, I just replaced the valve
for Zone1 as it had cracked, and all three zones worked for about a
week and now when the controller reaches zone3 the heads don't pop up
and it sounds like the water backs up (the copper pipe leading from the
house into the ground shakes quite violently and can no longer hear
running water). I am wondering if this might be most likely caused by
a clog in the sprinkler lines or a problem with the Zone3 valve or
something else. I have opened up the heads on the Zone3 sprinklers and
they are dry. Thank you for any suggestions you might have.


AppliancePartsPros.com, Inc.
Posted by Oren on July 18, 2006, 4:07 pm
wrote:

>I have a sprinkler system with three zones, I just replaced the valve
>for Zone1 as it had cracked, and all three zones worked for about a
>week and now when the controller reaches zone3 the heads don't pop up
>and it sounds like the water backs up (the copper pipe leading from the
>house into the ground shakes quite violently and can no longer hear
>running water). I am wondering if this might be most likely caused by
>a clog in the sprinkler lines or a problem with the Zone3 valve or
>something else. I have opened up the heads on the Zone3 sprinklers and
>they are dry. Thank you for any suggestions you might have.

I replaced a valve this Spring on a zone, and had similar situation. I
went back and the local guy gave me another valve...fixed it. YMMV.

Maybe a bad/stiff diaphragm.


Oren

Posted by Not@home on July 28, 2006, 7:41 pm
I think if there were debris in the lines downstream from the zone3
valve, at least some of the heads would get some water and work.

My guess would be that some debris got into the supply line (manifold)
upstream of the zone3 valve and is blocking flow to the valve and
everything downstream in that zone. Perhaps when the zone1 valve
cracked, a piece got into the line (or something got in while you were
replacing the zone1 valve) and lodged against the zone3 valve. Try
removing the zone3 valve and flushing the manifold; inspect the zone3
valve also to see if something lodged in there.

sweetft5 wrote:
> I have a sprinkler system with three zones, I just replaced the valve
> for Zone1 as it had cracked, and all three zones worked for about a
> week and now when the controller reaches zone3 the heads don't pop up
> and it sounds like the water backs up (the copper pipe leading from the
> house into the ground shakes quite violently and can no longer hear
> running water). I am wondering if this might be most likely caused by
> a clog in the sprinkler lines or a problem with the Zone3 valve or
> something else. I have opened up the heads on the Zone3 sprinklers and
> they are dry. Thank you for any suggestions you might have.
>

Similar ThreadsPosted
leaking sprinkler zone...what do i do? August 29, 2005, 6:08 pm
In-ground lawn sprinkler: one zone out of five doesn't work August 4, 2005, 7:44 pm
single zone sprinkler timer question/help April 15, 2007, 9:48 pm
Heat pump zone system July 16, 2006, 6:59 pm
Kinetico Sulfur Water Treatment System Failure November 14, 2006, 9:20 am
Re: sprinkler system June 23, 2005, 11:53 am
Re: sprinkler system June 23, 2005, 4:03 pm
Sprinkler System Help September 17, 2007, 4:44 pm
sprinkler system help needed June 3, 2006, 10:41 am
Sprinkler System Problem June 29, 2006, 3:56 pm

Contact Us | Privacy Policy

XML SitemapXML Sitemap