|
Posted by Chris Lewis on September 12, 2006, 12:08 pm
> GMT, peter wrote:
>
> > If a metal water pipe is bonded to ground at one point, can I then use the
> > other part of this pipe (e.g. on a different floor) as an extension of the
> > ground wire to retrofit 2-prong outlets into 3-prong ones?
>
> No. It's neither code, nor a good idea.
>
> You *can* use GFCIs to replace two prong outlets. You must attach a
> label that says "No equipment ground". You will find these labels
> included in the GFCI package.
>
> You can also use three prong outlets downstream of the GFCI. You must
> label these "GFCI protected", and "No equipment ground". You *cannot*
> connect a ground wire from the GFCI to the downstream outlets.
More clearly: you MUST NOT connect _anything_ to the ground lug
on the downstream outlets. In other words, you must not provide
any ground pin continuity between the ungrounded outlets.
If you do, a hot-ground fault on one device in one outlet, will
make all other grounded devices interconnected to that outlet
(via the illicit grounds to other outlets) live.
--
Chris Lewis, Una confibula non set est
It's not just anyone who gets a Starship Cruiser class named after them.
|