Posted by bc on July 17, 2005, 4:27 am
Is this a problem? The pad the compressor sits on seems to collect quite
a puddle, and there is some water standing in the bottom of the housing.
This is an outside unit, that is, a Carrier AC system with outside
compressor and coils, and lines running to an air handler inside. I
thought the cold part of things was the set of coils inside the air
handler. Thanks.
|

| |
Posted by TURTLE on July 17, 2005, 12:01 am
>
> Is this a problem? The pad the compressor sits on seems to collect quite
> a puddle, and there is some water standing in the bottom of the housing.
> This is an outside unit, that is, a Carrier AC system with outside
> compressor and coils, and lines running to an air handler inside. I
> thought the cold part of things was the set of coils inside the air
> handler. Thanks.
This is Turtle.
I can't say it sound bad just wet out there without looking at it to see other
things it could be wrong.
TURTLE
|
|
Posted by Rick on July 17, 2005, 5:49 am
>
> Is this a problem? The pad the compressor sits on seems to collect
quite
> a puddle, and there is some water standing in the bottom of the
housing.
> This is an outside unit, that is, a Carrier AC system with outside
> compressor and coils, and lines running to an air handler inside. I
> thought the cold part of things was the set of coils inside the air
> handler. Thanks.
If there's even a short section of the suction line exposed (no
insulation), it's probably just water condensing on the line and
running down to where it enters the unit..
|
|
Posted by Mikepier on July 17, 2005, 6:38 am
There are usually drain holes at the bottom of the unit which
occasionally get clogged and need to get cleaned out, if you have
access to it. I also have a Carrier and on my unit. If your unit is
similiar, I shut the power first, then I remove the fan shield on top
and can get access to the bottom and poke a long nail in the drain hole
to clear them.
If your condensate water gets pumped out of the house close to the
compressor, like mine, it could be what the water on the pad is from.
In that case you can just re-route it to drain further away.
|
|
Posted by SQLit on July 17, 2005, 6:37 am
>
> Is this a problem? The pad the compressor sits on seems to collect quite
> a puddle, and there is some water standing in the bottom of the housing.
> This is an outside unit, that is, a Carrier AC system with outside
> compressor and coils, and lines running to an air handler inside. I
> thought the cold part of things was the set of coils inside the air
> handler. Thanks.
Are you sure that the drain from the indoor unit does not come to the same
area?
|
Page 1 of 2 1 2 > last >>
| Similar Threads | Posted | | Dehumidifier Compressor Turns On, but Coils Don't Get Cold Enough | June 19, 2008, 9:58 pm |
| Condensing gas tank water heaters? | September 28, 2005, 12:07 am |
| Why no condensing tankless gas water heaters? | October 6, 2005, 11:24 am |
| stop water from condensing on gas pipe? | November 27, 2005, 8:52 am |
| Spray water on compressor to raise efficiency? | September 26, 2007, 8:13 pm |
| Refrigerator Coils | August 8, 2006, 1:24 pm |
| UV lights in AC coils? | March 1, 2008, 9:12 pm |
| Condensing Boiler | June 26, 2006, 5:03 pm |
| Question on cooling coils | August 27, 2005, 12:14 am |
| cleaning coils under the fridge | November 30, 2006, 10:51 am |
|
|